Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 1Models:QV32B-AQV36B-A• Do not store or use gasoline or other fl am-mable vapors and li
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0810A. Vent Termination Minimum ClearancesFire Risk.Explosion Risk.Maintain vent clearanc
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 11V= VENT TERMINALX= AIR SUPPLY INLET= AREA WHERE TERMINAL IS NOT PERMITTEDFigure 4.4
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0812Fire Hazard.Explosion Risk.Asphyxiation Risk.Do NOT connect this gas appliance to a ch
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 133in.CLEARANCETERMINATIONCAPFLEX-VENT1in.CLEARANCED. Use of Flex VentThe fl ex vent mus
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0814Fire Risk. Explosion Risk.Do NOT pack insulation or other combustibles between ceili
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 15Figure 5.5Top Vent - Horizontal TerminationVenting with 2 elbows (NG)Top Vent - Horiz
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0816Figure 5.6Top Vent - Horizontal TerminationVenting with 3 elbows (NG)Top Vent - Horizo
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 172. Top Vent - Vertical TerminationNo ElbowV1 = 60 ft. Max. (18.3 m)Figure 5.8INNER H
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0818Figure 5.9Top Vent - Vertical TerminationVenting with 2 elbows (NG)Top Vent - Vertical
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 19Figure 5.10Top Vent - Vertical TerminationVenting with 3 elbows (NG)Top Vent - Vertic
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/082CongratulationsListing Label Information/LocationModel Name: __________________________
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0820V1H1V2V3H22. Top Vent - Vertical Termination - (continued)Four 90º ElbowsV1 Min. H1
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 21Figure 5.12H1 = 24 in. (711 mm) MaximumRear Vent - Horizontal TerminationNo ElbowsRea
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0822 INS TALLE DHORIZON TAL LYRear Vent - Horizontal TerminationVenting with 3 elbo
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 23Figure 5.16V1H2H1INSTALLEDHORIZONTALLYRear Vent - Vertical TerminationVenting with 2
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08246 6 Vent Clearances and Framing A. Pipe Clearances to CombustiblesFire Risk.Explosi
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 25Figure 6.3 Exterior Wall Hole* Shows center of vent framing hole for top or rear ve
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0826C. Vertical Penetration FramingFigure 6.3Figure 6.4 Installing the Attic ShieldATTIC
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 27D. Install Attic Insulation ShieldWARNING! Fire Risk. DO NOT allow loose materials o
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0828A. Top VentFigure 7.2 Rotate the top heat shield to the vertical position as shown ab
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 29Figure 7.6 Remove the insulation from the outer vent pipe. Figure 7.7 To attach th
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 3Î = Contains updated information.Table of Contents1 Listing and Code Approvals A. A
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0830C. Securing and Leveling the ApplianceThe diagram shows how to properly position, lev
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 318 8 Installing Vent Pipe (DVP and SLP Pipe) A. Assemble Vent Sections (DVP Pipe O
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0832B. Assemble Vent Sections (SLP Pipe Only)To attach the fi rst vent component to the st
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 33D. Secure the Vent Sections• Vertical runs of DVP pipe must be supported every 8 ft
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0834F. Install Decorative Ceiling Components (SLP only)A decorative ceiling thimble can be
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 35G. Install Metal Roof FlashingNote: Skip this section if using the RF4-8.• See minim
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0836I. Install RF4-8The RF4-8 may be used in place of the roof fl ashing and storm collar (
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 37SCREWSCAULKSTORM COLLAR(1 of 3)Figure 8.23 Figure 8.23 TERMINATION CAPJ. Instal
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0838 Termination Cap Specifi cation Chart (depth without using additional pipe sections)SL
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 39Note: Have the gas supply line installed in accordance with local building codes, if
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/084B. Glass Specifi cationsHearth & Home Technologies appliances manufactured with temp
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0840Fire hazard. Do NOT change the valve settings.• This valve has been preset at the fac
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 41A. Recommendation for WireThis appliance requires 110-120 VAC be wired to the juncti
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0842WHTWHTBLKBLKGRN wire inside boxCopperground attachedto GRN screw withGRN wire14/2WGCov
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 43A. Mantel ProjectionsFigure 11.1 shows the minimum vertical and corresponding maximum
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0844B. Facing MaterialFire Risk.Do NOT obstruct air inlet or outlet grilles.Do NOT modify
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 4512 12 Appliance Setup A. Remove Shipping MaterialsRemove shipping materials from i
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0846E. Positioning the LogsIf the gas logs have been factory installed they should not ne
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 47STEP 1: Carefully remove the logs from the packaging. CAUTION: Logs are fragile! 2016
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0848Figure 12.14 Glass AssemblyF. Glass AssemblyRemoving Glass AssemblyPull the four glas
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 49A. Before Lighting ApplianceBefore lighting this appliance determine if it has a Stan
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 5G. Requirements for the Commonwealth of MassachusettsFor all side wall horizontally ve
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0850B. Lighting Appliance1. Turn off all electric power to the appliance if service is to
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 51Initial Break-in ProcedureWhen you light the appliance, you may notice that it pro-du
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0852A. Standing Pilot Ignition System14 14 Troubleshooting With proper installation, ope
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 53Troubleshooting (continued)Symptom Possible Cause Corrective Action3. Continued c. De
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/085415 15 Maintaining and Servicing Appliance Although the frequency of appliance servic
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 55Inspect Maintenance TasksDoors, Surrounds and Fronts1. Assess condition of screen a
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/085616 16 Reference Materials A. Appliance Dimension DiagramDimensions are actual appli
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 57B. Vent Components DiagramsFigure 16.2 DVP vent components 10-1/2 in.(267 mm)
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0858DVP-TRAP1DVP-TRAP2DVP-TRAPK1DVP-TRAPK2DVP-TRAPHorizontal Termination Cap15-1/8 in.(384
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 59B. Vent Components Diagrams (continued)Figure 16.4 DVP vent components13-1/4 in.(36
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/086A. Design and Installation ConsiderationsQuadra-Fire direct vent gas appliances are de
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0860EFFECTIVE HEIGHT/LENGTH8-3/4 in.222 mm6-1/2 in.165 mm6-5/8 in.168 mm6 in.152 mm6-1/2 i
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 61SLK-SNKDSnorkelTermination CapSLP-TVHWVerticalTermination CapSLP-FLEX-TRAPHorizontalT
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0862Service Parts DiagramQV32B-ABeginning Manufacturing Date: June 2003Ending Manufacturin
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 63IMPORTANT THIS IS DATED INFORMATION: When Requesting service or replacement parts for
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0864QV36B-AService Parts DiagramBeginning Manufacturing Date: June 2003Ending Manufacturin
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 65IMPORTANT THIS IS DATED INFORMATION: When Requesting service or replacement parts for
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0866Valve Assembly Parts ListQV32B-A, QV36B-ABeginning Manufacturing Date: June 2003Ending
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 67IMPORTANT THIS IS DATED INFORMATION: When Requesting service or replacement parts for
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/0868D. Limited Lifetime WarrantyLIMITED LIFETIME WARRANTYThe Hearth & Home Technologi
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 69Quadra-Fire, a brand of Hearth & Home Technologies Inc. 20802 Kensington Boulevar
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 73 3 Framing and Clearances Note:• Illustrations reflect typical installations and a
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/088Figure 3.2 Clearances to CombustiblesCBDAEHIFGJMEASURE FROMTOP OF UNIT OPENINGOR FROM
Quadra-Fire • QV32B-A, QV36B-A • 2014-900 Rev. J • 7/08 9D. Mantel Projections56789103451211109876TOP OF HOOD OR FIREPLACE OPENING412131132CEIL